Attached is a memo outlining some of the main changes to the proposed draft document IS10101 (now released for public comment)
Particular note to given to cable manufacturers and others.
* I.S.10101 – Chapter 5 – Selection and Erection of Equipment
Clause 512.1.5
The above Clause will require sign off by the appropriate person that the installation complies with the Electromagnetic Compatibility (EMC) Directive 2014/30/EU
http://eur-lex.europa.eu/legal-content/EN/TXT/?uri=CELEX:32014L0030&locale=en>.
The installation will of course apply only to the fixed wiring and switchgear, and not to any appliance connected after the isolator of socket.
Clause 527
The above Clause requires all cables to be rated Class Dca s1b,d2,a2 in accordance with EN50575.
I.S.10101 – Chapter 4 – Protection for Safety
Clause 411.3.4
Residual Current Devices (RCDs) will now be required to be installed on lighting circuits in domestic premises.
Clause 421.7
Arc Fault Detection Devices (AFDDs) will now be recommended for circuits installed in locations with particular risk.
LINK TO FULL DOCUMENT ON NSAI WEBSITE>>>>
(In order to make a comment you must be registered with “Your Standards Your Say” LINK HERE>>>)
The above are just some examples and your comments must be registered with NSAI at ‘Your Standards your Say’
You will have to register your association, company or individual to enter your comments